Critical Properties Guide for Relief Valve Sizing
- Paratherm Heat Transfer Fluids -

Critical Temperature, Tc
(Calculated)
Units NFİ HEİ ORİ MR™ MG™ LR™ CR™
şR 1453 1580 1524 1358 1357 1174 1168
şF 993 1120 1064 899 897 714 709
K 807 878 847 755 754 652 649


Critical Pressure, Pc
(Calculated)
Units NFİ HEİ ORİ MR™ MG™ LR™ CR™
ATM 11.12 26.5 13.34 12.93 12.46 10.69 28.63
PSIA 163 389 196 190 183 157 421


Critical Volume, Vc
(Calculated)
Units NFİ HEİ ORİ MR™ MG™ LR™ CR™
cm3/g-mole 1579 720 1380 987 1316 1327 493
ft3/lb 0.0722 0.0330 0.0632 0.0452 0.0602 0.0607 0.0226


Heat of Vaporization,
DH vap
Units NFİ HEİ ORİ MR™ MG™ LR™ CR™
BTU/lb 90.72 89.76 93 126.42 115 148 134.23


Molecular Weight avg Units NFİ HEİ ORİ MR™ MG™ LR™ CR™
MW 350 445 360 230 220 160 133


Constants

k=Cp/Cv =   1.01
C' =   316.5
R =   82.06 cm3*atm/mol*K
Z =   0.27
Fb 1.0

 