| Heat transfer oils are formulated to
move fast and carry maximum heat at
high temperatures. But the properties
that will optimize these performance
characteristics — low viscosity and
high density — also complicate efforts
to keep the fluids' molecules
contained at operating temperatures.
The very properties that make them
good heat transfer media also make
them prone to leakage.
Leak Detection
One of the simplest leak detectors for
thermal fluid
is the smoke that shows
up when the hot fluid is exposed to
air. The amount of smoke depends on
the size of the leak, the temperature of
the fluid and to some extent the
airflow in the area. Small oozing leaks
can produce an exaggerated amount
of smoke because there isn't enough
fluid to form a drop. This steady
weeping smokes and then cooks onto
the metal near the leak, leaving dark
stains, or - in time - a carbon crust.
With larger leaks, the fluid usually
cools quickly as it drips or sprays into
the air. Since smoke is actually the
reaction of the heat transfer fluid's
volatile low-boiling portions (smaller
molecules) with oxygen in the air, this
cooling reduces the vaporization of
fluid which helps lessen the amount of
smoke. However, if the leak is large
enough that its oxidation uses up all
the fresh air - or if ventilation is
insufficient - vapor can accumulate
and cause a potential fire hazard.
The key to preventing safety
problems from leaks
is to make sure
thermal fluid systems are not operated
in enclosed areas without adequate
ventilation. Ensure adequate fresh air
flow in any location (valves, flanges,
instrument ports, pumps, expansion
tanks, for example) where the
potential exists for a significant leak.
To Minimize Leaks
1. System Maintenance: Hot metal
increases in length (and diameter).
Bolts stretch. Piping runs increase
up to 4" per 100' of length. Hot fluid
is also much thinner than cold
(above 400°F, less viscous than
water at room temperature). In new
and old systems, the biggest
sources of leaks are flanges.
Leaking flanges should be
re-torqued. If you have to remove
the insulation to get to the flange,
make sure you read about
insulation fires in Paratherm's Fire
Prevention in Thermal Oil Heat
Transfer Systems technical data
sheet. Use fluorocarbon based
thread sealant or Teflon tape on
threaded fittings and tighten
them down.
2. Prevent Operator Error: All of the
drain valves should be closed
before adding fluid. All of the block
valves should be closed before
opening a line. Pressure gauges
should have isolating valves and be
located so that they cannot be
accidentally removed with a fork
truck. Leaking pump seals should
be replaced before they flush out
the bearing grease. The expansion
tank level should be checked
before startup.
Flash, Fire, and Autoignition
Points Demystified
Three major technical terms
describe flammability conditions in
hydrocarbon liquids and their
vapors; flash point, fire point, and
autoignition temperature.
Flash Point Defined
The lowest temperature at which a
heated liquid's vapor/air mixture can
be ignited ("flashed") by a flame or
spark, or other ignition source
placed above the liquid surface.
Fire Point Defined
The lowest temperature at which a
heated liquid's vapor/air mixture
will burn continuously when
combustion is supported by ignition
sources such as the above.
Autoignition Temperature
Defined
The temperature at which the vapor formed by a heated liquid will flash without a source of ignition.
Flash Point and Fire
Point Testing
The liquid to be tested is heated
in a cup and the rising liquid
temperature is continuously
measured. A small flame is
mechanically passed back and forth
just above the surface of the liquid.
As the liquid gets hotter, more of it
evaporates causing the fuel/air
mixture above the liquid to
gradually become richer. When the
lower flammability limit is reached,
the ignition source will ignite the
vapor/air mixture, causing a pop.
The observed temperature when the
flame momentarily ignites the
vapor/air mixture is the Flash Point.
The ignitions repeat as the liquid
temperature continues to rise. The
observed temperature when the
burning becomes continuous is the
Fire Point.
Autoignition Temperature Test
A sample is injected into a flask which is heated to the test temperature. If a “flash” is observed in the container, that temperature is the Auto Ignition Temperature. IF no flash is observed after a period of time, the flask temperature is increased and the test repeated. This method (ASTM E659-78) is valid only for fluids that are completely vaporized at the test temperature since the degradation products formed by any remaining liquid will affect the test result.
For a flash-point-related fire
to occur, all three conditions must
be met:
1) Vapor concentration - These
combustion tests allow vapor to
concentrate. In real life, the vapors
turn to smoke as they encounter
air and dissipate.
2) Temperature - Thermal oils cool
rapidly when exposed to air.
3) Source of ignition - Thermal-fluid
leaks are difficult to ignite unless a
significant amount of very hot
fluid leaks into a closed area
where inadequate ventilation
allows unreacted vapor to collect
and mix with air. An exception
occurs when fluid leaks onto an
extremely hot surface such as the
housing of a pump that is failing,
or a rotary union that has seized.
Technically, this is not a flashpoint-related problem but one of
autoignition.
Heat Transfer Fluids in closed-loop
systems, whether natural or
synthetic, are routinely used well
in excess of their flash and fire
points.
Subscribe to the Hot-Oil/System User's Guide Today! |
You'll receive one of these User's Guide data sheets every three weeks, and receive notice via email when Paratherm publishes new white papers, technical data sheets, and hot-oil-system tipsheets.
|
Questions? We'd like to hear from you. Call toll-free, 800-222-3611 -- or fax or e-mail. |