Critical Properties Guide for Relief Valve Sizing
- Paratherm Heat Transfer Fluids -

Critical Temperature, Tc
(Calculated)
Units NF© HE© OR© MR™
ºR 1453 1580 1524 1358
ºF 993 1120 1064 899
K 807 878 847 755


Critical Pressure, Pc
(Calculated)
Units NF© HE© OR© MR™
ATM 11.12 26.5 13.34 12.93
PSIA 163 389 196 190


Critical Volume, Vc
(Calculated)
Units NF© HE© OR© MR™
cm3/g-mole 1579 720 1380 987
ft3/lb 0.0722 0.0330 0.0632 0.0452


Heat of Vaporization,
DH vap
Units NF© HE© OR© MR™
BTU/lb 90.72 89.76 93 126.42


Molecular Weight avg Units NF© HE© OR© MR™
MW 350 445 360 230


Constants

k=Cp/Cv =   1.01
C' =   316.5
R =   82.06 cm3*atm/mol*K
Z =   0.27
Fb 1.0

 